Skip to content

Full-Stack Energy Management

From the cell up.
One architecture.

Starts at the cell: 1500 V BMS, designed for IEC 61508 SIL 2 and ISO 26262 ASIL B. Plant control runs at the edge, fully autonomous when connectivity drops; IT/OT separation enforced in hardware, NIS2 compliant by design. Portfolio monitoring runs in the cloud.

In production today

Monitored. Controlled. Protected.

Energy capacity under management across the plants we operate; measured at every layer of the stack.

Monitoring

138 MWh

through EMS Cloud + EMS Gateway

Live portfolio visibility and edge control across connected plants.

Protecting

70 MWh

by BMS 1500V

Cell-level safety enforced in hardware and firmware.

Products

The full
energy stack.

Three products built as a system. Plant-level intelligence runs locally on the Gateway; local SCADA, energy flow visualization, and Power Plant Controller (PPC) functions operate independently of cloud connectivity. Portfolio-level monitoring and profile management run in the cloud. The separation is intentional: OT data stays on the OT network, aligned with NIS2 and IEC 62443 requirements. The data chain from cell-level BMS measurements and asset serial numbers through to the cloud historian is structured for EU Battery Passport compliance.

Plant view — OT layer

EMS Gateway · Local SCADA

Single-line diagram, energy flow, equipment status. Runs locally. Available without cloud connectivity.

Portfolio view — IT layer

EMS Cloud · Multi-site monitoring

Historian, events, profile management across all sites. OT data stays on the OT network; NIS2 compliant by design.

01 / EMS CLOUD

EMS Cloud

Portfolio View · IT-layer Monitoring

Portfolio-level monitoring across all plants from a single interface. Covers meters, PV inverters, battery systems, and battery inverters; data stored at 1-minute intervals with analytics from 1-minute to monthly aggregations, custom ranges, and exportable reports. Uptime monitoring tracks both network connectivity and equipment operational status across all plants. Push notifications with programmable thresholds: over-temperature, over-voltage, disconnected devices. The cloud layer manages profiles and historian data only; operational data is processed on the Gateway and stays on the OT network by design. Accessible as a PWA; no installation required.

Monitoring
Meters · PV · battery inverters · BESS
Analytics
1 min to monthly · custom ranges · reports
Uptime
Connectivity · equipment operational status
Notifications
Push · programmable thresholds
Profiles
Self-consumption · scheduling · compensation
Access
Web · PWA

02 / EMS GATEWAY

EMS Gateway

Plant View · OT-layer Intelligence

Industrial edge node that runs the plant. Integrates field devices over Modbus TCP/IP, Modbus RTU, IEC 60870-5-101/104, OPC UA, and CAN; covering the full range of protocols in industrial automation and energy infrastructure. Acts as a Modbus server with configurable register mapping; existing SCADA systems connect without modification while the field layer is replaced below. Functions as a PPC; executes active power, curtailment, and compensation profiles locally, independent of cloud connectivity. Local SCADA with single-line diagram: all field devices as nodes, energy flow and equipment status visualized with color-coded link states. Dual GbE interfaces enforce IT/OT network separation in hardware, a direct architectural requirement under NIS2 for energy infrastructure operators.

Protocols
Modbus TCP/IP · Modbus RTU · IEC 60870-5-101/104 · OPC UA · CAN
Network
2 × 2.5 GbE (IT/OT separation)
Serial
2 × RS232/RS485
Local SCADA
SLD, energy flow, node status
Platform
Fanless industrial compute · multiple variants
Operating temp
0 to 60 °C (reference)
Modbus Server
Configurable register mapping · SCADA passthrough

03 / BMS 1500V

BMS 1500V

Battery Management System

High-voltage battery management system for C&I energy storage and utility-scale BESS. Modular SMU/CMU architecture. Protection is implemented in hardware and firmware: dual high-voltage contactors with auxiliary feedback, pre-charge circuit, and a 200 A fast-acting fuse on the positive line. Designed to IEC 61508 SIL 2 and ISO 26262 ASIL B targets by engineers from automotive embedded development. BMS Control Center and BMS Viz Tool included.

Max DC bus
1500 V
Current
±500 A, galvanically isolated
Cell Accuracy
2 mV
CMU Cells
4 to 18 per CMU
CMU Scale
Up to 32 CMUs per SMU
Network Scale
Up to 63 SMUs
Interfaces
Modbus TCP/IP · SunSpec
Safety Targets
IEC 61508 SIL 2 · ISO 26262 ASIL B

Partner with us

For installers
& integrators.

The Nokto stack is available under two commercial models. Deploy it under the Nokto brand, or available white-label under the integrator's own brand. Both models include the same hardware, software, and engineering support.

Partner

Nokto-branded

Deploy the full stack under the Nokto brand. Our brand remains visible to end customers as the technology vendor. Standard partner pricing.

  • EMS Cloud UI: Nokto branding
  • EMS Gateway: Nokto hardware labeling
  • BMS 1500V: Nokto logo on the PCB and SMU enclosure
  • Full documentation and technical support
  • Nokto-managed software updates included

OEM

White-label

The full stack under the integrator's brand. Logo, hardware labeling, cloud UI, and documentation carry the partner's identity. End customers see the partner brand, not ours. OEM pricing applies.

  • EMS Cloud: Partner's branding and domain
  • EMS Gateway: Partner's hardware labeling
  • BMS 1500V: Partner's logo on the PCB silkscreen and SMU enclosure
  • Documentation rebranded under the partner's name
  • Partner's resident engineer: Direct access to our infrastructure for independent update management

Get in touch

about how we can help you.

Tell us about your project. We typically respond within one business day.

Or write directly to contact@nokto.eu